The IP5009 SSI interface module allows an SSI encoder to be connected directly. The encoder is powered via the SSI interface. The interface circuit generates a pulse for reading the encoder and makes the incoming data stream available to the controller as a data word in the process image. The module can optionally provide the data as binary numbers or as a binary gray code. Various operating modes, transmission frequencies and bit widths can be permanently stored in a control register.
Product status:
service phase | Possibly with other technical features or equipment in case of a service order or repair
Product information
| Technical data position measurement | IP5009-Bxxx |
|---|---|
| Connection technology | M23 connector with outer thread, 12-pin |
| Number of channels | 1 |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Signal input | difference signal (RS485) |
| Encoder supply | 24 V DC, from load voltage |
| Sensor supply | from control voltage, max. 0.5 A, short-circuit proof in total |
| Data transfer rates | variable up to 1 MHz, 250 kHz default |
| Serial input | 24 bits (adjustable) |
| Data direction | read |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Current consumption from US (without sensor current) | see documentation |
| Bit width in the process image | input: 1 x 32 bit data (1 x 8 bit control/status optional) |
| Electrical isolation | depends on the bus system |
| Technical data | IP5009-B200 |
|---|---|
| Extension modules | – |
| Digital peripheral signals | according to I/O type |
| Analog peripheral signals | according to I/O type |
| Configuration | via KS2000 or the controller |
| Data transfer rates | 2.5 Mbaud |
| Bus interface | 2 x fiber-optic socket for plug ZS1020-0010 |
| Data transfer medium | fiber-optic conductor: APF (plastic) fiber (1,000 µm) |
| Power supply | control voltage: 24 V DC (-15%/+20%); load voltage: according to I/O type |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Auxiliary power current | according to I/O type |
| Electrical isolation | control voltage/fieldbus: yes, control voltage/inputs or outputs: according to I/O type |
| Distance between stations | 45 m |
| Data transfer time | 0.26 ms in the case of 10 modules for 32 bit input and output each (without IP-Link) |
| Weight | approx. 250 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
| Approvals/markings | CE, UL |
| Housing data | XXL housing |
|---|---|
| Dimensions (W x H x D) | 30 mm x 210 mm x 26.5 mm |
| Material | PA6 (polyamide) |
| Installation | 2 fixing holes 3.5 mm diameter for M3 |
Loading content ...