The KL2652 output terminal has two relays, each featuring a change-over contact. The relay contact can be used universally for switching devices requiring mains power up to 230 V AC or 300 V DC. The KL2652 Bus Terminal is equipped with potential-free contacts. The signal state of the Bus Terminal is indicated via LEDs.
Product status:
regular delivery
Product information
| Technical data | KL2652 |
|---|---|
| Number of outputs | 2 x change-over |
| Nominal voltage | 230 V AC (max. switching voltage 250 V AC/300 V DC) |
| Switching voltage max. | 250 V AC, 300 V DC |
| Load type | ohmic, inductive, lamp load |
| Max. output current | 5 A per channel |
| Switching current | max. 1 A AC/1 A DC at 40 V DC; max. 0.15 A at 300 V DC (UL: max. 230 V AC, 1 A) |
| Minimum permitted load | 100 mA at 12 V |
| Lamp test, electronic ballast | max. 6 A starting current |
| Electrical isolation | 1.5 kV (K-bus/field potential); 2.5 kV rated surge voltage, overvoltage category III |
| Current consumption power contacts | – |
| Current consumption K-bus | typ. 90 mA |
| Bit width in the process image | 2 outputs |
| Max. switching frequency | 6/min. (at rated load) |
| Operating cycles mech. (min.) | 5 x 106 |
| Operating cycles electr. (min.) | 1 x 106 (1 A/250 V AC) |
| Configuration | no address or configuration setting |
| Special features | reverse switching realizable |
| Weight | approx. 55 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Plug-in wiring level | for all KSxxxx Bus Terminals |
| Approvals/markings | CE, UL |
| Housing data | KL-12-8pin | KS-12-8pin |
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
| Stripping length | 8…9 mm | 9…10 mm |
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| KL2652 | Bus Terminal, 2-channel relay output, 230 V AC, 300 V DC, 1 A |
| KS2652 | Bus Terminal, 2-channel relay output, 230 V AC, 300 V DC, 1 A, pluggable wiring level |